State Environmental Planning Policy (Exempt and Complying Development Codes) 2008
Historical version for 4 June 2010 to 10 June 2010 (accessed 23 May 2013 at 03:14) Current version

5.8   Development standards

The standards specified for that development are that:
(a)  the development must be located at least 3.5m behind the building line from any lot boundary, and
(b)  the development must be designed so as not to emit noise exceeding an LAeq of 5 dB(A) above background noise when measured at any lot boundary, and
(c)  the development must be located not more than 1m above the ridge of a pitched roof or 3m above a flat roof, and
(d)  the development must not relate to the cooking of food at the premises by barbecue or charcoal methods, and
(e)  any demolition necessary must be carried out in accordance with AS 2601—2001, Demolition of structures.
Note. If the mechanical ventilation system is a regulated system in regulated premises within the meaning of the Public Health Act 1991, the system must comply with the requirements of that Act, including AS/NZS 3666.1:2002, Air-handling and water systems of buildings—Microbial control—Design, installation and commissioning.