5.8 Development standards
The standards specified for that development are that:(a) the development must be located at least 3.5m behind the building
line from any lot boundary, and
(b) the development must be designed so as not to emit noise exceeding
an LAeq of 5 dB(A) above background noise when measured at any lot boundary,
and
(c) the development must be located not more than 1m above the ridge
of a pitched roof or 3m above a flat roof, and
(d) the development must not relate to the cooking of food at the
premises by barbecue or charcoal methods, and
(e) any demolition necessary must be carried out in accordance with
AS 2601—2001,
Demolition of structures.
Note. If the mechanical ventilation system is a regulated
system in regulated
premises within the meaning of the Public Health Act 1991, the system
must comply with the requirements of that Act, including AS/NZS 3666.1:2002, Air-handling
and water systems of buildings—Microbial control—Design,
installation and commissioning.